Potential Study of Solar Thermal Cooling in Sub-Mediterranean Climate

dc.contributor.authorJaradat, Mustafa
dc.contributor.authorAl-Addous, Mohammad
dc.contributor.authorAlbatayneh, Aiman
dc.contributor.authorDalala, Zakariya
dc.contributor.authorBarbana, Nesrine
dc.date.accessioned2020-06-17T11:43:01Z
dc.date.available2020-06-17T11:43:01Z
dc.date.issued2020-04-01
dc.date.updated2020-05-07T06:34:15Z
dc.description.abstractAir conditioning is becoming increasingly important in the energy supply of buildings worldwide. There has been a dramatic increase in energy requirements for cooling buildings in the Middle East and North Africa (MENA) region. This is before taking the effects of climate change into account, which will also entail a sharp increase in cooling requirements. This paper presents the potential of using a solar thermal absorption cooling system in Sub-Mediterranean Climate. Four sites in Jordan are now equipped with water-lithium bromide (H2O-LiBr) absorption chillers with a total nominal capacity of 530 kW. The focus of the paper was on the pilot system at the German Jordanian University (GJU) campus with a cooling capacity of 160 kW. The system was designed and integrated in order to support two existing conventional compression chillers with a nominal cooling capacity of 700 kW. The system was economically evaluated based on the observed cooling capacity results with a Coefficient of Performance (COP) equals 0.32, and compared with the values observed for a COP of 0.79 which is claimed by the manufacturer. Several techniques were implemented to evaluate the overall economic viability in-depth such as present worth value, internal rate of return, payback period, and levelized cost of electricity. The aforementioned economic studies showed that the absorption cooling system is deemed not feasible for the observed COP of 0.32 over a lifespan of 25 years. The net present value was equal to −137,684 JD and a payback period of 44 years which exceeds the expected lifespan of the project. Even for an optimal operation of COP = 0.79, the discounted payback period was equal to 23 years and the Levelized Cost of Electricity (LCOE) was equal to 0.65 JD/kWh. The survey shows that there are several weaknesses for applying solar thermal cooling in developing countries such as the high cost of these systems and, more significantly, the lack of experience for such systems.en
dc.description.sponsorshipDFG, 414044773, Open Access Publizieren 2019 - 2020 / Technische Universität Berlinen
dc.identifier.eissn2076-3417
dc.identifier.urihttps://depositonce.tu-berlin.de/handle/11303/11432
dc.identifier.urihttp://dx.doi.org/10.14279/depositonce-10313
dc.language.isoenen
dc.rights.urihttps://creativecommons.org/licenses/by/4.0/en
dc.subject.ddc600 Technik, Technologiede
dc.subject.otherthermally driven refrigerationen
dc.subject.otherabsorption chillersen
dc.subject.othersolar collectorsen
dc.subject.othersolar air conditioningen
dc.subject.otherfeasibility studyen
dc.subject.otherpresent worth valueen
dc.subject.otherpayback perioden
dc.titlePotential Study of Solar Thermal Cooling in Sub-Mediterranean Climateen
dc.typeArticleen
dc.type.versionpublishedVersionen
dcterms.bibliographicCitation.articlenumber2418en
dcterms.bibliographicCitation.doi10.3390/app10072418en
dcterms.bibliographicCitation.issue7en
dcterms.bibliographicCitation.journaltitleApplied Sciencesen
dcterms.bibliographicCitation.originalpublishernameMDPIen
dcterms.bibliographicCitation.originalpublisherplaceBaselen
dcterms.bibliographicCitation.volume10en
tub.accessrights.dnbfreeen
tub.affiliationFak. 3 Prozesswissenschaften::Inst. Technischen Umweltschutz::FG Umweltverfahrenstechnikde
tub.affiliation.facultyFak. 3 Prozesswissenschaftende
tub.affiliation.groupFG Umweltverfahrenstechnikde
tub.affiliation.instituteInst. Technischen Umweltschutzde
tub.publisher.universityorinstitutionTechnische Universität Berlinen

Files

Original bundle
Now showing 1 - 1 of 1
Loading…
Thumbnail Image
Name:
applsci-10-02418-v2.pdf
Size:
6.89 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
4.9 KB
Format:
Item-specific license agreed upon to submission
Description:

Collections